Your Generator Is Only as Reliable as Its Last Service

A standby generator that has not been properly maintained is not a backup power system. It is a liability. Facility managers, property developers, and operations leaders across Texas trust Current Power Technologies to keep their commercial and industrial power infrastructure in peak condition through structured, SLA-driven maintenance contracts that eliminate guesswork and guarantee accountability.

With 500+ active generator service contracts under management across San Antonio, Austin, and Houston, our team brings the experience, tools, and licensed expertise to handle any commercial system, regardless of brand or who installed it.

Our Commercial Service Structure

CPT commercial maintenance follows a two-level inspection framework matched to your facility operational requirements and risk profile.

Level 1 Inspection

(Semi-Annual)

Performed twice per year, covering all critical operating systems

  • Engine Electrical & Starting System: Battery load testing, alternator inspection, battery charger voltage check, starting motor test.

  • Generator Inspection: Winding inspection, bearing lubrication check, brushes and diodes, circuit breaker test, mounts and bolts.

  • Safety Controls & Control Panel: AC/DC voltage and frequency measurement, auto start/stop verification, shutdown and pre-alarm testing.

  • Instrumentation: Oil pressure, water temperature, and amperage measurement. Control panel wiring inspection.

  • Air Induction & Exhaust: Air filter inspection, turbocharger check, exhaust and silencer inspection.

  • Lubrication System: Oil level check, crankcase breather, fuel lines, seals, and gaskets.

  • Cooling System: Radiator core, coolant level and freeze point, hoses, fan assembly, water pump, jacket water heater.

  • Fuel System: Fuel lines and connections, fuel filters, carburetor/mixer, day tank and fuel cell inspection.

  • ATS (Automatic Transfer Switch): Wiring and contacts, infrared temperature scan, contactor operation test, timer and control verification.

Level 2 Inspection & Engine Service (Annual)

All Level 1 tasks, plus full engine service

  • Fuel System: Fuel filter and fuel/water separator replacement.

  • Lubrication System: Oil filter replacement, full oil drain and refill with fresh engine oil, independent oil sample analysis.

  • Generator: Bearing lubrication where applicable.

Our Commercial Service Structure

Annual PM Program

  • Two visits per year: 1x Level 1 Inspection + 1x Level 2 full engine service

  • Flat annual rate, all PM labor included

  • Invoiced upon completion of each scheduled service, Net 30 days

  • Agreement renews annually unless canceled in writing 30 days prior to renewal

Emergency Call-Out

  • Standard rate: 50/hr

  • After-hours rate: 95/hr

  • Invoiced upon completion of each scheduled service, Net 30 days

  • Parts and materials: Cost + 30%, quoted prior to replacement

Workmanship Warranty

  • CPT warrants all workmanship for 30 days following each service visit. Manufacturer warranties apply to all OEM parts replaced.

What Our Customers Say

“We just recently had our 1st annual preventative maintenance on our Kohler generator. Chris was very informative, thorough, and professional. He went through all the necessary maintenance updates along with all the pressure checks. We are very satisfied with Current Power Technologies and their skilled personnel. When it comes to generators I highly recommend Current Power Technologies.”
Carol Spears

“Ingram performed our regular maintenance. He communicated well with us, he was on-time, efficient, professional, and explained what he was doing. We are very happy with Ingram and the service we are receiving from Current Power Tech.”

Cheryl Gowens

“Matthew, with Current Power Technologies, arrived early, did an outstanding job, helped me with the App, cleaned when done and was professional and courteous as usual. Really appreciate this company, their people and great service! Thank You all!”

Steve Mills
Commercial Generator Maintenance.

Switch Your Current Maintenance Provider

Already have a system in place? You do not need to replace your equipment to get better service.

Current Power Technologies can take over maintenance, testing, inspections, and compliance support for your existing commercial power system, regardless of who originally installed it.

  • NFPA 110 Compliance: We design service plans to keep your facility compliant with required testing intervals and documentation standards.

  • Load Bank Testing: Full-load performance validation confirming your generator will carry its rated capacity when it matters.

  • Priority Response: Local, Texas-licensed Master Electricians who answer the phone and show up.

  • Multi-Site Portfolios: Standardized preventive care for property managers across Central and Southeast Texas.

  • Authorized Service: Factory-trained on Generac and Kohler. Capable of servicing all major commercial brands.

Industries We Serve

  • Healthcare campuses and medical facilities

  • Data centers and mission-critical IT infrastructure

  • Manufacturing and industrial facilities

  • Warehouse and cold storage operations

  • Multi-family residential developments

  • Commercial office buildings and retail centers

  • Restaurants, hospitality, and educational facilities

Request a Commercial Maintenance Audit

Our team will assess your existing system, review your current service history, and recommend a maintenance contract structured around your facility operational requirements and compliance obligations.

Commercial Generator Maintenance & SLAs FAQs

A: Yes. Current Power Technologies can assume the maintenance, testing, and compliance management of your existing commercial power system regardless of who originally installed it. Our licensed Master Electricians are equipped to service all major commercial generator brands.

A: We recommend a Level 1 inspection semi-annually and a full Level 2 engine service annually. High-use or mission-critical facilities may require more frequent service intervals based on runtime hours and operational risk profile.

A: We recommend a Level 1 inspection semi-annually and a full Level 2 engine service annually. High-use or mission-critical facilities may require more frequent service intervals based on runtime hours and operational risk profile.